          Comprehensive Product Information Advantages Comprehensive Transformer Design Informaiton Specification Sheet for Torodial Transformers Quality in Design & Production Bridgeport Magnetics News & Press Releases Schedule of Trade Shows Contact Bridgeport Magentics The History of Bridgeport Magentics Frequently Asked Questions Bridgeport Magentics Site Map
 
Ask us a Question...
 

Toroidal Power Transformers
for 117V/60Hz Operation

In Stock Standard Designs

  • Primary Voltage:                      117V
  • Operating Frequency:               60 Hz
  • Power Range:                          30 VA 40,000 VA
  • Dual Secondary Voltages:         No Charge, As Specified 
  • Dimensions and Weight            Click Here
  • Insulation System:                   Class A (105 C)
  • Mounting Hardware:                  Click Here
  • Safety Standard Certifications: UL506, CSA C22.2 No.66-1988, EN 61558-1, IEC61558-1, IEC742 and come with CE marking. Intertek File:  3051384
  • Any combination of secondary windings may be specified
    for our standard designs.
  • No engineering design charges.

 

Contact us for a Free Transformer Design Review

Request a Price Quote
 

 


In Stock
117V / 60Hz Toroidal Power Transformers
for Industrial and Commercial Applications
 
Power
Rating
VA
P/N   Dimensions* Weight* Mounting Hardware
 Frequency OD. x HT    in.  mm lbs.    kg
30 TD030 60Hz 2.6 x 1.4 66 x 36 1.1 0.5 Washer/ pad size: 1
60 TD060 60Hz 3.2 x 1.5 81 x 38 1.7 0.8 Washer/ pad size: 2
120 TD120 60Hz 3.9 x 1.6 99 x 41 2.4 1.1 Washer/ pad size: 3
180 TD180 60Hz 4.3 x 1.7 109 x 43 3.4 1.6 Washer/ pad size: 3
240 TD240 60Hz 4.5 x 1.9 114 x 48 4.4 2.0 Washer/ pad size:  4
300 TD300 60Hz 4.7 x 2.1 119 x 53 5.4 2.5 Washer/ pad size:  4
360 TD360 60Hz 5.0 x 2.3 127 x 59 6.2 2.8 Washer/ pad size:  4
480 TD480 60Hz 5.2 x 2.5 132 x 64 3.4 1.5 Washer/ pad size:  5
575 TD575 60Hz 5.3 x 2.6 135 x 66 3.7 1.7 Washer/ pad size:  5
600 TD600 60Hz 5.4 x 2.8 137 x 71 8.8 4.0 Epoxy potted center w/ 1/4" hole
720 TD720 60Hz 5.7 x 2.9 145 x 74 10.3 4.7 Epoxy potted center w/ 1/4" hole
900 TD900 60Hz 6.3 x 2.8 160 x 71 12.7 5.8 Epoxy potted center w/ 1/4" hole
1,200 TD1200 60Hz 6.6 x 3.0 168 x 76 15.4 7.0 Epoxy potted center w/ 1/4" hole
1,560 TD1560 60Hz 7.0 x 3.0 178 x 76 19.0 8.6 Epoxy potted center w/ 1/4" hole
2,050 TD2050 60Hz 8.0 x 3.0 203 x 76 23.0 10.4 Epoxy potted center w/ 1/4" hole
2,360 TD2360 60Hz 8.5 x 3.5 216 x 89 29.0 13.2 Epoxy potted center w/ 1/4" hole
3,600 TD3600 60Hz 9.5 x 3.5 241 x 89 33.0 15.0 Epoxy potted center w/ 1/4" hole
4,800 TD4800 60Hz 9.8 x 4.0 249 x 102 42.0 19.1 Epoxy potted center w/ 1/4" hole
6,600 TD6600 60Hz 11.0 x 4.5 279 x 114 62.0 28.1 Epoxy potted center w/ 1/4" hole
9,000 TD9000 60Hz 13.0 x 5.0 330 x 127  76.0 34.5 Epoxy potted center w/ 1/4" hole
12,000 TD12000 60Hz 13.5 x 6.0 343 x 152 110.0 49.9 Epoxy potted center w/ 1/4" hole
18,000 TD18000 60Hz 15.0 x 6.0 381 x 152 150.0 68.0 Epoxy potted center w/ 1/4" hole
24,000 TD24000 60Hz 16.0 x 6.5 406 x 165 195.0 88.5 Epoxy potted center w/ 1/4" hole
40,000 TD40000 60Hz         Epoxy potted center w/ 1/4" hole

Request a Price Quote

* Based on design with dual secondaries. Please call for final dimensions and weight.

Safety Standard Certifications:
UL506, CSA C22.2 No.66-1988, EN 61558-1, IEC61558-1, IEC742
and come with CE marking. Intertek File: 3051384

Standard Mounting Methods

A metal washer and rubber pads provide the most economical way of mounting the transformer horizontally and is adequate for transformers under 600 VA, provided the transformer is not installed in a product that receives rough handling.  Above 600 VA, epoxy potted center is standard mounting method.  Prices include mounting hardware, either a steel washer and two rubber pads or as shown for larger sizes, an epoxy potted center with one or two drilled mounting holes.

  • Optional Potted Center

For a nominal cost you can order smaller transformers with epoxy potting, either with drilled hole or threaded inserts. The potting has a recessed top to accommodate screw head. Flat bottom is a standard feature.

  • The L-Bracket
    An L-shaped steel bracket is an economical solution for vertical mounting. A metal washer and two rubber pads are furnished with each L-bracket.
    Larger transformers will have an epoxy potted center.

 

Standard Sizes of Steel Washers

Dimensions in Inches

Size

A

B

C

T

D

1

2.00

.75

.188

.04

.18

2

2.38

.88

.188

.05

.22

3

2.75

1.13

.25

.06

.26

4

3.50

1.25

.25

.06

.28

5

4.38

1.38

.31

.08

.33

6

5.70

1.75

.31

.08

.50

Standard Washers


      Home | Product Search | Advantages | Design Guide | Design Help

        Product Quality | News | Trade Shows | Contact Us |
About Us | TermsFAQ | Site Map

    "All technical data, prices, terms and conditions are subject to change without prior notice."
    Copyright 2012 -
    Bridgeport Magnetics Group, Inc.  All rights reserved
    No part of this site may be copied or reproduced without expressed written consent